Certificates of compliance stating that the fittings or gaskets
used for waste drains or lines designated on the plans as [_____]
are [oil] [_____] resistant.
1.5
DELIVERY, STORAGE, AND HANDLING
1.5.1
Delivery and Storage
1.5.1.1
Piping
Inspect materials delivered to site for damage; store with minimum of
handling. Store materials on site in enclosures or under protective
coverings. Store [plastic piping and jointing materials and] rubber
gaskets under cover out of direct sunlight. Do not store materials
directly on the ground. Keep inside of pipes and fittings free of dirt and
debris.
1.5.1.2
Metal Items
Check upon arrival; identify and segregate as to types, functions, and
sizes. Store off the ground in a manner affording easy accessibility and
not causing excessive rusting or coating with grease or other objectionable
materials.
1.5.1.3
Cement, Aggregate, and Reinforcement
**************************************************************************
NOTE: Delete these paragraphs if not used or insert
applicable concrete requirements here.
**************************************************************************
As specified in Section [03300A CAST-IN-PLACE STRUCTURAL CONCRETE] [03300N
CAST-IN-PLACE CONCRETE].
1.5.2
Handling
Handle pipe, fittings, and other accessories in such manner as to ensure
delivery to the trench in sound undamaged condition. [Take special care
not to damage linings of pipe and fittings; if lining is damaged, make
satisfactory repairs.] Carry, do not drag, pipe to trench.
1.6
DRAWINGS
**************************************************************************
NOTE: Include subparagraph c. on NASA projects.
**************************************************************************
a. Submit Installation Drawings showing complete detail, both plan and
side view details with proper layout and elevations.
b. Submit As-Built Drawings for the complete sanitary sewer system
showing complete detail with all dimensions, both above and below
grade, including invert elevation.
c. Sign and seal As-Built Drawings by a Professional Surveyor and
Mapper. Include the following statement: "All potable water lines
crossed by sanitary hazard mains are in accordance with the permitted
utility separation requirements."
SECTION 02531