1.4
ENVIRONMENTAL REQUIREMENTS
Connecting hardware shall be rated for operation under ambient conditions
of 0 to 60 degrees C 32 to 140 degrees F and in the range of 0 to 95
1.5
QUALIFICATIONS
1.5.1
Minimum Contractor Qualifications
Work under this section shall be performed, and equipment shall be
furnished and installed, by a qualified Contractor as defined herein. The
Contractor shall have a minimum of two years of experience in the
installation and testing of coaxial cable-based TV distribution systems and
equipment. Installers assigned to the installation of this system or its
components shall have a minimum of two years of experience in the
1.5.2
Minimum Manufacturer Qualifications
The equipment and hardware provided under this contract shall be products
of manufacturers that have a minimum of two years of experience in
producing the types of systems and equipment specified.
1.6
DELIVERY AND STORAGE
Equipment delivered and placed in storage shall be stored with protection
from the weather, humidity and temperature variation, dirt and dust or
1.7
SPARE PARTS
The Contractor shall submit spare parts data for each different item of
later than [2] [_____] months prior to the date of beneficial occupancy.
The data shall include a complete list of parts and supplies, with current
unit prices and source of supply, and a list of spare parts recommended for
stocking.
PART 2
PRODUCTS
2.1
MATERIALS AND EQUIPMENT
**************************************************************************
NOTE: Ensure that the NEC requirement for 40
percent maximum fill of conduit and other raceways
is met when sizing raceways.
For cables which require special jackets, such as
those subject to corrosive environments, provide a
description of the environmental requirements.
Select the appropriate cable jacket rating based on
NEC or local code requirements. If there is a
potential for mixed rating of the same cables, use
the highest rating only.
**************************************************************************
SECTION 16815A
Page 7