to 300 MHz. Drop cable connectors shall be of a type specifically designed
for use with aluminum foil shielded cable and shall incorporate a uniformly
crimped sleeve for shield connection. Connections to tap and terminal
devices shall conform to the established standards for BNC connectors.
Jacket materials shall resist the effects of sunlight and oxidation for a
period of at least 10 years non-contaminating. Drop cables used in
underground applications shall be further protected by a moisture resisting
flooding compound applied between the shield and the jacket. The flooding
compound shall be electrically non-conductive, non-corrosive, and as
recommended by the cable manufacturer.
2.4
CABLE CONNECTORS
2.4.1
Foam-Filled Rigid
Terminating connectors used to terminate foam-filled rigid coaxial cable
shall incorporates an integral radiation suppressing sleeve supporting the
aluminum sheath. Provide adapting connectors to adapt the terminating
connector to match the connector type required for connection to
amplifiers, taps, and splitters and end-of-link equipment. Connector cable
retention force shall not be less than the cable manufacturer's maximum
pulling tension specification. Impedance of terminating connectors and
on which installed.
2.4.2
Flexible and Semi Rigid
Connectors for RG/58 and RG/11 coaxial cable shall be bayonet connectors
(BNC). Connectors shall be either crimp-on or solder type.
2.5
RACEWAY SYSTEMS
**************************************************************************
NOTE: The designer will show on the drawings which
specific type of raceways are needed.
**************************************************************************
Raceway systems as specified in Section 16402 INTERIOR DISTRIBUTION SYSTEM
and Section 16375A ELECTRICAL DISTRIBUTION SYSTEM, UNDERGROUND and as shown
shall be furnished and installed.
2.6
ENCLOSURES
**************************************************************************
NOTE: The designer will show on the drawings which
specific type of enclosure is needed.
**************************************************************************
Metal enclosures shall be provided as needed for equipment not housed in
racks or supplied with a housing. Enclosure finish color shall be
manufacturer's standard, unless otherwise indicated. Damaged surfaces
shall be repaired using original type finish. The enclosures shall be as
specified or shown.
2.6.1
Interior
Enclosures used in an interior environment shall meet the requirements of
NEMA 250, Type 12.
SECTION 16794A
Page 20