[COAXIAL CABLE PARAMETERS
TYPE RG-11
Minimum Bend Radius:
102 mm (4.0 in) or greater value per
cable manufacturer's recommendations]
COAXIAL CABLE PARAMETERS
TYPE RG-6
Inner Conductor:
18 American wire Gauge
Solid bare copper wire of nominal diameter
[[____] mm] [0.040 inch]
68 degrees F of 21.0 ohms per km
([_____] ohms per foot)
Dielectric Core:
Foam FEP
Nominal Diameter of 4.32 mm (0.170 inch)
Outer Conductor:
Duofoil + 95% tinned copper braid coverage
minimum
Maximum Diameter of 5.94 mm (0.234 inch)
Jacket:
Black, Non-contaminating
Polyvinylchloride (PVC)
Velocity of Propagation:
83 percent nominal
Eccentricity:
10 percent maximum
53.1 picofarads per m, (16.2 pF/ft) maximum
13.1 decibels
per 100 m, (4.0 db/100 ft)
maximum at
0.36 Gigahertz
25.6 decibels
per 100 m, (7.8 db/100ft)
maximum at
1 Gigahertz
TYPE RG-11
Conductor:
30 American wire Gauge
Standard, tinned copper, nominal diameter of
0.305 mm (0.012 in)
degrees C (68 degrees F) of 0.33 ohms per km
(0.1 ohms per foot)
Insulation Material:
Foamed high density polyethylene, nominal
diameter of 1.47 mm (0.058 in)
Shield Type and Coverage:
Tinned copper braid, 89% coverage
Jacket:
Manufacturer's recommendation as required
for installed location (e.g., plenum,
riser, general), nominal diameter of
2.46 mm (0.097 in)
Velocity of Propagation:
78% nominal
SECTION 16794A
Page 18