2.5.2
Distribution Amplifier
Distribution amplification shall be provided as required to deliver the
minimum signal parameters specified in paragraph SYSTEM DESCRIPTION and
TABLES IIa and IIb to user interfaces. Distribution amplifier shall be
designed for heavy duty commercial and industrial applications. As a
minimum, amplifier shall be contained in a wall-mountable steel or aluminum
housing, vented or finned for convection cooling. Amplifier cable ports
shall be "F" type. External RF test points shall be provided to monitor
signals without opening the housing. Amplifier may be powered through the
cable or by a 120 Vac, 60 Hz source. Surge protection module shall be
provided on outside cable entry ports. Cable powered amplifier shall be
capable of passing a maximum of 10 amperes through cable ports without
damage. The individual components, amplifiers, filters, splitters, pads,
equalizers and automatic level control circuitry shall be modular in
construction and shall plug into the main RF chassis.
2.5.3
The signal distribution system power supply required for cable powered
amplifiers shall be 100 percent plug-in modular construction and shall
standby type with sealed batteries supplied. Power supply shall be housed
in a fully weatherproofed steel cabinet, and shall as a minimum conform to
the following specifications:
Input Voltage:
95-130 Vac, 60 Hz
Output Voltage:
30 or 60 Vac as required by amplifier
Output Current:
12 amperes @ 30 or 60 Vac
Line Regulation:
Plus or minus 2 percent, 95 - 130 Vac
Local Regulation:
Plus or minus 2 percent, 1/3 of full load
Noise Level:
Less than 48 dB at 300 mm 1 foot distance
PART 3
EXECUTION
3.1
INSTALLATION
Interior installations shall comply with NFPA 70. Exterior installations
shall comply with IEEE C2, NFPA 70, and NFPA 780. System components shall
be installed and tested in accordance with the manufacturer's
specifications and recommendations.
3.1.1
Head End Equipment
The components comprising the head end equipment shall be
located as shown.
Grounding of the system shall comply with NFPA 70. Rack
mounted head end
equipment shall be mounted at least 900 mm 36 inches from
any wall. Head
end equipment shall be aligned to meet system performance
and
manufacturer's requirements.
3.1.2
Distribution System
The Contractor shall configure the distribution system components in a
SECTION 16785A
Page 19