rack with uprights to mount equipment [482 mm 19 inches] [584 mm 23 inches]
wide and standoff brackets for wall mounting. Standoff brackets shall be
of sufficient length for a [152 mm 6 inch] [_____] clearance between rack
and wall. Uprights shall be drilled and tapped 12-24 in a 13 mm 1/2 inch
pattern. Rack shall be hinged. Rack shall be [clear coated] [painted].
Color shall be the manufacturer's standard.
2.3.3
Cabinet
Equipment rack cabinet shall be free standing steel enclosure with side
panels, [acrylic plastic] [perforated] [louvered] [metal] front doors,
[perforated] [louvered] metal rear doors, depth-adjustable front and rear
mounting rails, and [solid] [louvered] top. Cabinet shall mount equipment [
482 mm 19 inches] [584 mm 23 inches] wide. Cabinet shall be 1829 mm 72
inches high and 762 mm 30 inches deep and shall be provided with [leveling
feet] [wheels]. Cabinet exterior shall be [painted] [clear coated]. Color
shall be the manufacturer's standard.
2.3.4
Cable Guide
Cable guide shall be specifically manufactured for the purpose of routing
cables and wires horizontally and vertically on the supplied equipment
racks. Cable guide shall consist of ring or bracket-like devices mounted
on rack panels for horizontal use or individually mounted for vertical use.
Cable guide shall be mounted to rack using screws and/or nuts and
2.4
EQUIPMENT BACKBOARD
**************************************************************************
NOTE: When equipment backboards are used in the
system, the designer will locate and dimension the
backboards on the drawings.
**************************************************************************
Equipment backboard, where shown, shall be Type ACX plywood coated on both
sides with at least two coats of insulating varnish, sized and located as
shown.
2.5
PREMISES DISTRIBUTION SYSTEM
**************************************************************************
NOTE: The designer will coordinate requirements for
ancillary components required in the design with
SECTION 16815A CABLE TELEVISION PREMISES
DISTRIBUTION SYSTEM.
**************************************************************************
2.5.1
General
The coaxial cabling from outlets to the head end equipment location
shall be installed in accordance with SECTION 16815A CABLE TELEVISION
PREMISES DISTRIBUTION SYSTEM. Components required by this section shall be
coordinated by the contractor in order to ensure satisfactory operation of
the installed system.
SECTION 16785A
Page 18