2.1.12
Psychiatric Room Entrance Station (AVS)
[Wall recessed] [Surface mounted] corridor switch for use with special
treatment areas, as indicated.
2.1.13
Psychiatric Patient Bed Station (AVS)
**************************************************************************
NOTE: Consult with the user to determine if either
a radio system or a nurse assist button will be
required.
**************************************************************************
[Wall recessed] [Surface mounted] tamperproof station, with facilities for
normal and emergency call origination, and accommodations to selectively
control call origination capabilities.
2.1.14
[Wall recessed] [Desk top] master station annunciator and control station,
for handling up to [_____] calling stations, with the following performance
features:
a.
Basic Operating Requirements (AVS): Station shall provide
standard audio-visual call registration and response features for
use with associated patient, staff, and duty stations.
Additionally, station shall provide for visual registration for
other calling stations. Separate distinguishable tones shall be
provided to identify the priority status of incoming calls.
**************************************************************************
NOTE: At the text below, discuss the standard dome
light colors and flashing schemes with the user. If
the standard is not adequate, modify to suit the
project. Notify the AIC/EIC of any variance from
the standard.
**************************************************************************
b.
Call Priorities (AVS): Station shall be equipped to handle
standard types of priority level calls as listed below:
Priority
Call Type
Level
Dome Light Indication
Code Blue
1
Flashing Blue
Code Call
1
Flashing Red
Nurse Assist
2
Flashing White, Steady Green
Emergency
3
Flashing White
Patient--Priority
3
Flashing White
Patient--Personal Attention
4
Steady White
Patient--Normal Call
4
Steady White
[Nurse Service
Flashing Green]
[Aide Service
Flashing Amber]
**************************************************************************
NOTE: At the text below, use
program-controlled features are needed by the user.
**************************************************************************
SECTION 16725N