SD-08 Manufacturer's Instructions
Qualifications of service facility
Manufacturer recommendations for protection of stored equipment
Manufacturer recommendations for protection of equipment from
supply-line transients
SD-10 Operation and Maintenance Data
Nurse call systems, Data Package 5
Submit in accordance with Section 01781 OPERATION AND
MAINTENANCE DATA.
SD-11 Closeout Submittals
Operating manuals
1.5
QUALITY ASSURANCE
1.5.1
Regulatory Requirements
Nurse call systems and equipment shall conform to UL 1069 and meet
requirements of the specified application.
1.5.2
Manufacturer Standard
Equipment shall be standard products of the same manufacturer, shall be the
latest design by the manufacturer, and shall have been designed by the
manufacturer to operate as a complete system for the intended use.
1.5.3
Service Facility
**************************************************************************
NOTE: Generally, the 4-hour response time shown
bracketed should be suitable for most projects.
Consult with the AIC/EIC on projects at remote
locations.
**************************************************************************
Equipment shall be supplemented by a factory authorized service
organization, reasonably convenient to the site, which will provide service
at the site within [4] [_____] hours after service is requested.
1.5.4
Subsystem Equipment Requirements
conform to UL 1069. The UL label or listing will be acceptable as evidence
of compliance.
1.6
STORAGE AND PROTECTION
Protect stored equipment as recommended by the manufacturer.
1.7
SUPPLY-LINE TRANSIENTS
Protect equipment from supply-line transients as likely to be subjected in
SECTION 16725N
Page 8