Posted Instructions[; G][; G, [_____]]
Proposed diagrams, instructions, and other sheets shall be
SD-06 Test Reports
Field Quality Control
a. Upon completion and testing of the installed system,
performance test reports are required in booklet form showing all
field tests performed to adjust each component and all field tests
performed to provide compliance with the specified performance
criteria. Each test shall indicate the final position of controls.
b. Field test reports shall be written, signed and provided as
each circuit or installation item is completed. Field tests shall
include resistance-to-ground and resistance between conductors,
and continuity measurements for each circuit. For each series
circuit the input voltage and output current of the constant
multiple circuits the input and output voltage of the transformer
for each intensity setting shall be measured. A visual inspection
of the lights operation, or of the markings appearance, or of the
installation of fixtures or units installed shall be reported.
Visual Inspection
Inspection reports shall be prepared and provided as each stage
of installation is completed. These reports shall identify the
activity by contract number, location, quantity of material
placed, and compliance with requirements.
SD-07 Certificates
Qualifications
Certified documentation of qualifications, as specified.
Materials and Equipment
When equipment or materials are specified to conform to the
standards or publications and requirements of AASHTO, ANSI, ASTM,
AEIC, FM, IEEE, IES, NEMA, NFPA, or UL, or to an FAA, FS, or MS,
proof that the items furnished under this section of the
specifications conform to the specified requirements shall be
included. The label or listing in UL Elec Const Dir or in FM
P7825a, FM P7825b or the manufacturer's certification or published
catalog specification data statement that the items comply with
applicable specifications, standards, or publications and with the
manufacturer's standards will be acceptable evidence of such
compliance. Certificates shall be prepared by the manufacturer
when the manufacturer's published data or drawings do not indicate
conformance with other requirements of these specifications.
SD-10 Operation and Maintenance Data
Operation and Maintenance Procedures
SECTION 16526A
Page 12