63.5 mm (1 x 2-1/2 inches) 1 x 2-1/2 inches minimum with minimum 6.4 mm
(1/4 inch) 1/4 inch high normal block lettering. Nameplates shall be
provided as indicated. Nameplates shall be fastened to the device with a
minimum of two sheet metal screws or two rivets.
2.1.3
Conduit, Conduit Fittings, and Boxes
2.1.3.1
Rigid Steel or Intermediate Metal Conduit (IMC) and Fittings
The metal conduit and fittings shall be UL 6 and UL 1242, respectively,
coated with a polyvinylchloride (PVC) sheath bonded to the galvanized
exterior surface, nominal 1.0 mm (40 mils) 40 mils thick, conforming to
NEMA RN 1.
2.1.3.2
Flexible Metal Conduit
Flexible metal conduit shall be UL 1, zinc-coated steel.
Use UL 360
liquid-tight flexible metal conduit in wet locations.
2.1.3.3
Outlet Boxes for Use with Steel Conduit, Rigid or Flexible
These outlet boxes shall be UL 514A, cast metal with gasket closures.
2.1.3.4
Plastic Duct for Concrete Encased Burial
These ducts shall be [PVC conforming to NEMA TC 6 & 8, Type EB]
[provided
as specified in Section 16375A, ELECTRICAL DISTRIBUTION SYSTEM,
UNDERGROUND].
2.1.3.5
Plastic Conduit for Direct Burial
This plastic conduit shall be [PVC conforming to NEMA TC 2 (conduit) and
NEMA TC 3 (fittings) Type [EPC-40 PVC] [EPC-80 PVC]] [provided as specified
in Section 16375A, ELECTRICAL DISTRIBUTION SYSTEM, UNDERGROUND].
2.1.3.6
Frangible Couplings and Adapters
These frangible couplings shall be in accordance with FAA DWG C-6046.
Provide upper section of frangible coupling with one of the following:
a.
Unthreaded for slip-fitter connections.
b.
61.1 mm (2-13/32 inch) 2-13/32 inch - 16N-1A modified thread for
c.
53 mm (2 inch) 2 inch - 11 1/2-N.P.T. (tapered) with 5.6 mm (7/32)
7/32 inch nominal wall thickness to accept rigid conduit coupling.
d.
Frangible Couplings for specialized applications as approved.
e.
Electrical Metallic Tubing UL 797 where indicated for use with
frangible couplings and adapters.
2.1.4
Wire and Cable
Conductors shall be copper except as otherwise indicated.
SECTION 16525A
Page 14