e.
Fused Cable Connectors. Provide connector consisting of a line-
side receptacle and a load side plug, each in a molded rubber form
and including crimp-on fittings for the cable ends to accommodate
a 250-volt cartridge-type fuse. Provide fuse with rating
indicated. Provide connectors in kit form properly sized for the
specific cable diameter involved. Completed connection shall be
watertight.
2.1.4.5
Cable Tags
Cable tags for each cable or wire shall be installed at duct entrances
entering or leaving manholes, handholes, and at each terminal within the
lighting vault. Cable tags shall be stainless steel, bronze, lead strap,
or copper strip, approximately 1.6 mm (1/16 inch) 1/16 inch thick or hard
plastic 3.2 mm (1/8 inch) 1/8 inch thick suitable for immersion in salt
water and impervious to petroleum products and shall be of sufficient
length for imprinting the legend on one line using raised letters. Cable
tags shall be permanently marked or stamped with letters not less than 6.4
mm (1/4 inch) 1/4 inch in height as indicated. Two-color laminated plastic
is acceptable. Plastic tags shall be dark colored with markings of light
color to provide contrast so that identification can be easily read.
Fastening material shall be of a type that will not deteriorate when
exposed to water with a high saline content and to petroleum products.
2.1.4.6
Concrete Markers for Direct Buried Cable Systems
Concrete markers shall be as specified in Section 16375A, ELECTRICAL
DISTRIBUTION SYSTEM, UNDERGROUND.
2.1.5
Ground Rods
Ground rods shall be sectional copper-clad steel with diameter adequate to
permit driving to full length of the rod, but not less than 19.1 mm (3/4
inch) 3/4 inch in diameter and 3.048 m (10 feet) 10 feetlong, unless
indicated otherwise.
2.1.6
These lightning arresters shall be in accordance with IEEE C62.11 and IEEE
C62.41 as applicable with ratings as indicated.
2.1.7
Cable Connectors and Splices
Cable connectors in accordance with FAA AC 150/5345-26, Item L-823 shall be
used for connections and splices appropriate for the type of cable. Other
types of cable connectors and splices shall be of copper alloys for copper
conductors, aluminum alloys for aluminum-composition conductors and a type
conductors. For FAA Type L-824 lighting cable, connectors shall be FAA AC
150/5345-26, Type L-823.
2.1.8
**************************************************************************
needed to support helipad systems. Prepare this
paragraph as necessary to suit the specific helipad
installation.
SECTION 16525A
Page 16