9.
Slow close/open breaker and check for binding.
10. Perform time-travel analysis.
11. Verify tightness of accessible bolted connections by calibrated
torque-wrench method. Thermographic survey[ is not][ is] required.
12. Record as-found and as-left operation counter readings.
b.
Electrical Tests
1.
Measure contact resistances.
2.
3.
Verify trip, close, trip-free, and antipump functions.
4.
3.5.1.4
a.
Visual and mechanical inspection
1.
Compare equipment nameplate data with specifications and approved
shop drawings.
2.
Inspect physical and mechanical condition.
Check for damaged or
[3.
Verify that cooling fans operate correctly and that fan motors
have correct overcurrent protection.]
[4.
Verify operation of all alarm, control, and trip circuits from
temperature and level indicators, pressure relief device, and
5.
Verify tightness of accessible bolted electrical connection by
calibrated torque-wrench method. Thermographic survey[ is not][
is] required.
6.
7.
Perform specific inspections and mechanical tests as recommended
by manufacturer.
8.
Verify correct equipment grounding.
b.
Electrical Tests
1.
2.
Perform turns-ratio tests.
3.
Perform insulation power-factor/dissipation-factor tests on
windings.
4.
Sample insulating liquid.
Sample shall be tested for:
(a)
Dielectric breakdown voltage
SECTION 16361N
Page 44