the voltage rating and burden needed.
**************************************************************************
Voltage transformers shall have indicated ratios. Units shall have an
accuracy class rating of [_____]. Voltage transformers shall be of the
drawout type having current-limiting fuses in both primary and secondary
circuits. Mechanical interlocks shall prevent removal of fuses, unless the
associated voltage transformer is in a drawout position. Voltage
transformer compartments shall have hinged doors.
2.9
AUXILIARY SUBSTATION EQUIPMENT
2.9.1
Voltage Regulator
**************************************************************************
NOTE: Bypass arresters are normally standard
equipment. Incoming line arresters may not be
needed. Coordinate with manufacturer.
**************************************************************************
Voltage regulators shall comply with IEEE C57.15 and shall be of the
outdoor, self-cooled, 55/65 degrees C temperature rise, [single-phase]
[three-phase] station-type. Two single-phase units connected in open-delta
are not acceptable. Windings and the load-tap-changing mechanism shall be
mineral-oil-immersed. When operating under load, a regulator shall provide
percent steps, with 16 steps above and 16 steps below rated voltage.
Automatic control equipment shall provide Class 1 accuracy. Bypass surge
arresters shall be suitable for [a grounded] [an ungrounded] system and for
the associated regulator voltage. [Station] [Intermediate] class surge
arresters shall be mounted next to each incoming line bushing on a
regulator tank-mounted bracket and connected to a surge arrester ground
pad-mounted on the regulator tank.
2.9.1.1
Ratings
Ratings at 60 Hz shall be:
Maximum voltage.............................................[_____]
BIL.........................................................[_____]
Current.....................................................[_____]
2.9.1.2
Bypass and Isolation Switches
Switches shall be of the outdoor, stick-operated, single-pole,
single-throw, vertical-break type suitable for the indicted mounting. One
switch stick of adequate length shall be provided. Switches shall be of a
type designed to provide bypass of a single-phase regulator circuit by an
integral sequence which always occurs when each switch is opened or closed.
Each opening sequence shall initially bypass the single-phase regulator
circuit, then open the input and output circuits, and finally interrupt the
exciting current. Opening any single-phase regulator circuit shall not be
possible until after the bypass circuit is closed. Unless the voltage
protectors shall be mounted across terminals of each switch rated up to 25
kV.] [station-class surge arresters shall be provided to protect each phase
of 35 kV switches.] Ratings at 60 Hz shall be in accordance with IEEE
SECTION 16311A