transformer neutral [grounding resistor] current transformer].
m.
Directional overcurrent relay, device 67N.
n.
One three-phase or three single-phase transformer differential
relays, device 87T, and an auxiliary lockout relay, device 86T,
o.
One three-phase or three single-phase bus differential relays
device 87B, and an auxiliary lockout relay, device 86B, arranged
p.
[Single-] [Three-] phase secondary potential test blocks with
associated test devices, quantity as shown.
q.
[Single-] [Three-] phase secondary current test blocks with
associated test devices, quantity as shown.
r.
Key-interlocking shall be provided with the primary disconnecting
switch serving the associated transformer.
s.
[_____].
2.7.11.2
Auxiliary Compartments
**************************************************************************
NOTE: Where switchgear aisle space of sufficient
will be mounted there. Coordinate with NFPA 70 and
IEEE C2 for clearances. The designer should
indicate the panelboard requirements on the project
drawings.
**************************************************************************
Control and instrument transformers and panelboards shall be provided and
housed in compartments, [unless otherwise noted,] and shall supply control
power and instrument voltage to each bus section of the switchgear lineup
and remote devices as required. Compartments shall be provided with a
hinged door. Any interconnection wiring and conduit needed to connect the
switchgear lineup or other devices requiring control power or instrument
items shall include the following:
a.
[Three] [_____] potential transformers.
b.
c.
[_____] low-voltage alternating-current panelboards and [_____]
low-voltage direct-current panelboards with main and branch
circuits as shown [, located in the switchgear aisle where
indicated] [, and with equipment as specified in paragraph
AUXILIARY SUBSTATION EQUIPMENT].
d.
[_____].
SECTION 16311A
Page 52