UPS SYSTEM PERFORMANCE DATA SHEET
SHEET 4 OF 6
_______________________________________________________________________________
ITEM
SPECIFIED
SUBMITTED
_______________________________________________________________________________
LOAD SHARING
+/- 5.0% OF AVERAGE LOAD
AMONG MODULES
_________________________________________________________________
VOLT. TRANSIENT
RESPONSE
50% STEP LOAD
0% to 50%
+/- 8.0%
______________________________________________
50% STEP LOAD
50% to 100%
+/- 8.0%
______________________________________________
LOSS OR RETURN
OF INPUT
+/- 1.0%
______________________________________________
LOSS OR RETURN
OF A REDUNDANT
MODULE
AUTOMATICALLY
+/- 8.0%
______________________________________________
MANUALLY
+/- 8.0%
______________________________________________
A
AUTO TRANSFER,
C
AT FULL LOAD,
FROM UPS TO
+/- 4.0%
O
BYPASS
______________________________________________
U
T
MANUAL TRANS-
P
FER, AT FULL
U
LOAD, FROM
+/- 4.0%
T
BYPASS TO UPS
______________________________________________
RECOVERY TIME
TO 99% STEADY-
50 MILLISECONDS
STATE COND.
______________________________________________
+/- 0.5 Hz
IENT RESPONSE
_________________________________________________________________
SLEW RATE
1.0 Hz/SECOND
_______________________________________________________________________________