UPS SYSTEM PERFORMANCE DATA SHEET
SHEET 3 OF 6
_______________________________________________________________________________
ITEM
SPECIFIED
SUBMITTED
_______________________________________________________________________________
VOLTAGE, LINE-LINE [_____] V
_________________________________________________________________
PHASES
3-PHASE, 4-WIRE
_________________________________________________________________
POWER FACTOR
0.8 LAGGING, 1.0
_________________________________________________________________
VOLTAGE REGULATION
BALANCED LOAD
+/- 1.0%
______________________________________________
50% IMBALANCE
+/- 2.0%
BETWEEN PHASES ______________________________________________
NO-LOAD
MODULATION
+/- 1.0%
______________________________________________
DRIFT (30 DAYS)
+/- 1.0%
_________________________________________________________________
VOLTAGE ADJUST.
+/- 5.0% MANUALLY
_________________________________________________________________
A
60 Hz
C
_________________________________________________________________
REGULATION
+/- 0.1%
O
______________________________________________
U
DRIFT (24 HRS.)
+/- 0.1%
T
_________________________________________________________________
P
U
TOTAL (50% NON-LINEAR LOAD
7.0% MAX.
T
TOTAL (LINEAR LOAD)
5.0% MAX.
3.0% MAX.
_________________________________________________________________
PHASE DISPLACEMENT
BALANCED LOAD
+/- 1.0 DEG. OF BYPASS
______________________________________________
50% IMBALANCE
+/- 3.0 DEG. OF BYPASS
_________________________________________________________________
WAVE FORM
DEVIATION FACTOR
5.0%
(NO LOAD)
_________________________________________________________________
OVERLOAD CAPACITY
125%
10 MINUTES
______________________________________________
150%
30 SECONDS
______________________________________________
300%
MOMENTARY
_______________________________________________________________________________
SECTION 16265A
Page 45