3.2.1.2
Wall
Wall supports for pipe shall be made by suspending the pipe from
appropriately sized Type 33 brackets with the appropriate ceiling and roof
3.2.2
Flanges shall be Class 125 type, drilled, and of the proper size and
configuration to match the equipment and diesel engine connections.
3.2.3
Cleaning
After fabrication and before assembly, piping interiors shall be manually
wiped clean of debris.
3.2.4
Pipe Sleeves
Pipes passing through construction such as ceilings, floors, or walls shall
be fitted with sleeves. Each sleeve shall extend through and be securely
fastened in its respective structure and shall be cut flush with each
surface. The structure shall be built tightly to the sleeve. The inside
diameter of each sleeve shall be minimum 13 mm 1/2 inch, and where pipes
pass through combustible materials 25 mm 1 inch larger than the outside
3.3
ELECTRICAL INSTALLATION
Electrical installation shall comply with NFPA 70, IEEE C2, and Section
16402 INTERIOR DISTRIBUTION SYSTEM. For vibration isolation, flexible
fittings shall be provided for conduit, cable trays, and raceways attached
to engine-generator sets; metallic conductor cables installed on the engine
generator set and from the engine generator set to equipment not mounted on
the engine generator set shall be flexible stranded conductor; and
terminations of conductors on the engine generator set shall be crimp-type
terminals or lugs.
3.4
FIELD PAINTING
**************************************************************************
NOTE: For Air Force work, add that the exterior of
all equipment shall be finished in the base standard
color.
**************************************************************************
Field painting shall be as specified in Section 09900 PAINTS AND COATINGS.
3.5
ONSITE INSPECTION AND TESTS
3.5.1
Test Conditions
3.5.1.1
Data
Measurements shall be made and recorded of all parameters necessary to
verify that each set meets specified parameters. If the results of any
test step are not satisfactory, adjustments, replacements, or repairs shall
be made and the step repeated until satisfactory results are obtained.
Unless otherwise indicated, data shall be recorded in 15 minute intervals
SECTION 16263A
Page 73