application. Provide plan and elevation drawings of
the remote control panels for prime power
applications, depicting specific devices,
instrument, and meters, including layouts.
indication may be added if required (Not available
for standard molded-case breakers. Use only for
Edit the table to include all required devices.
Delete all columns except the first column and the
appropriate reference columns (always delete the
"MFG Offering" column).
A remote stop switch is required by NFPA 37 for 100
hp and above engines, and by NFPA 110 for both Level
1 and Level 2 applications. A remote fuel shutoff
switch, and a remote lube-oil shutoff switch are
required by NFPA 37 for 100 hp and above engines.
Delete the remote fuel shutoff switch, and a remote
lube-oil shutoff switch where not required.
**************************************************************************
accordance with [NFPA 110 level [1] [2]]] [and as follows] mounted [either
on or adjacent to the engine generator set] [as indicated]. A remote
control panel shall be provided [with devices as indicated] [fully
Device/Condition/
Corps
NFPA 110
NFPA 110
MFG
Function
Requirement
Level 1
Level 2 Offering
Controls
Switch: run/start -
CP
CP/STD
off/reset - auto
Emergency stop switch
CP
CP/STD
& alarm
Lamp test/indicator
CP
CP VA
CP VA
CP/STD
test
Common alarm contacts/
X
X
CP/O
Panel lighting
CP
CP/STD
Audible alarm &
CP
silencing/reset
switch
Voltage adjust for
CP
CP/STD
voltage regulator
Pyrometer display
CP
w/selector switch
Remote emergency stop
CP VA
CP VA
switch
Remote fuel shutoff switch
Remote lube-oil shutoff switch
2.18.2
Engine Generator Set Metering and Status Indication
**************************************************************************
NOTE: Delete the remote (control room) panel if the
SECTION 16263A
Page 60