Overload Capacity
110% of Service Load for
(Prime applications only)
1 hour in 12 consecutive hours
Service Load
[_____] kVA (maximum)
[_____] kVA (continuous
Motor Starting kVA (Max.)
[_____] kVA
Power Factor
[0.8] [_____] lagging
Engine-Generator Applications
[stand-alone]
[parallel with infinite bus]
[parallel with other
generators on an isolated bus]
[parallel with other generators
on an infinite bus]
Maximum Speed
[_____] [900] [1200] [1800] rpm
[fin-tube (radiator)]
[shell-tube]
[Governor Type
Isochronous
+ [_____] [0.4] [0.25] %
(steady state)]
[Governor Type
Droop
[3] [_____] % (maximum)
(No Load to Full Load)
+ [_____] [0.4] [0.25] %
(steady state)]
+ 2% (maximum)
(No Load to Full Load)
(Stand alone applications)
+ [0.5] [1] [2] %
(steady state)
Frequency
[50] [60] Hz
Voltage
[_____] volts
Phases
[3 Phase, Wye] [3 Phase, Delta]
[_____] %
Subtransient Reactance
Nonlinear Loads
[_____] kVA
Max Step Load Increase
[25] [50] [75] [100] % of
Service Load at [_____] PF
Transient Recovery Time
[_____] seconds
SECTION 16263A
Page 26