4.
Perform a capacity load test.
3.5.1.5
a.
Visual and mechanical inspection
1.
Compare equipment nameplate data with specifications and approved
shop drawings.
2.
Inspect physical and mechanical condition.
3.
Inspect for correct anchorage and grounding.
b.
Electrical and mechanical tests
1.
2.
Perform phase rotation test to determine compatibility with load
requirements.
3.5.1.6
Grounding System
a.
Visual and mechanical inspection
1.
Inspect ground system for compliance with contract plans and
specifications.
[b.
Electrical tests
**************************************************************************
NOTE: For SOUTHNAVFACENGCOM projects, delete
"Electrical tests" below.
**************************************************************************
1. Perform ground-impedance measurements utilizing the
fall-of-potential method. On systems consisting of interconnected
On systems consisting of a single ground rod perform tests before
any wire is connected. Take measurements in normally dry weather,
not less than 48 hours after rainfall. Use a portable ground
testing megger in accordance with manufacturer's instructions to
test each ground or group of grounds. The instrument shall be
equipped with a meter reading directly in ohms or fractions
thereof to indicate the ground value of the ground rod or
grounding systems under test.]
3.5.2
Functional Acceptance Tests
**************************************************************************
NOTE: Include the bracketed option below for
LANTNAVFACENGCOM projects.
**************************************************************************
The tests shall be performed by the start-up engineer. Upon successful
test completion, the start-up engineer shall provide the Contracting
Officer with a written test report within 15 calendar days showing the
tests performed and the results of each test. The report shall include the
completed approved test data forms and certification from the start-up
SECTION 16237N
Page 44