[Six] [_____] certified copies of the results of a "Complete
Test" for duplicate equipment will be accepted in lieu of the
"Complete Test" as specified in subparagraph COMPLETE TEST for
equipment of the respective rating and type. No substitute will
be accepted for the "Check Test."
SD-10 Operation and Maintenance Data
Instructions
[Six] [_____] copies of complete instructions for the proper
installation, inspection, and maintenance of the machines
provided for this particular service. Instruction manuals shall
be submitted to the Contracting Officer not later than the date
the equipment is shipped from the manufacturer's plant. The
instructions shall include a cross-sectional drawing indicating
the major component parts of the motor and the procedure for
disassembly.
1.3
SYSTEM DESCRIPTION
The work under this section includes providing all labor, equipment, and
material and performing all operations required to design, manufacture,
driving pumps specified under Section 15131A VERTICAL PUMPS, AXIAL-FLOW AND
MIXED-FLOW IMPELLER TYPE. These motors shall be supplied complete with all
accessories, spare parts, tools, and manufacturer's data and instructions
as specified herein.
1.4
GENERAL REQUIREMENTS
1.4.1
The equipment provided under these specifications will be subjected to
severe moisture conditions and shall be designed to render it resistant to
corrosion from such exposure. The general requirements to be followed to
mitigate corrosion are specified below. Any additional special treatment
under the respective item. However, other corrosion-resisting treatments
that are the equivalent of those specified herein may, with the approval of
the Contracting Officer, be used.
1.4.1.1
Fastenings and Fittings
Where practicable, all screws, bolts, nuts, pins, studs, springs, washers,
and other similar fittings shall be of corrosion-resisting material or
shall be treated in an approved manner to render them resistant to
corrosion.
1.4.1.2
Corrosion-Resisting Materials
Corrosion-resisting steel, copper, brass, bronze, copper-nickel, and
nickel-copper alloys are acceptable corrosion-resisting materials.
1.4.1.3
Corrosion-Resisting Treatments
Hot-dip galvanizing shall be in accordance with ASTM A 123/A 123M or ASTM A
153/A 153M as applicable. Other corrosion-resisting treatments may be used
if approved by the Contracting Officer.
SECTION 16221A
Page 7