supported by a service organization.
2.2
ASBESTOS PROHIBITION
Asbestos and asbestos-containing products shall not be used.
2.3
NAMEPLATES
All equipment shall have a nameplate, installed by the manufacturer, that
identifies the manufacturer's name, address, type or style, and model or
serial number.
2.4
EQUIPMENT GUARDS AND ACCESS
**************************************************************************
NOTE: Catwalks, ladders, and guardrails may be
required. If so, select the applicable item and
indicate on drawings. If not applicable, delete the
entire sentence.
**************************************************************************
Belts, pulleys, chains, gears, couplings, projecting setscrews, keys, and
other rotating parts exposed to personnel contact shall be fully enclosed
or guarded according to OSHA requirements. High temperature equipment and
piping exposed to contact by personnel or where it creates a potential fire
hazard shall be properly guarded or covered with insulation of a type
specified. The requirements for [catwalks,] [operating platforms,]
[ladders,] [and] [guardrails] are specified in Section [05500A
MISCELLANEOUS METAL] [05500N METAL FABRICATIONS].
2.5
ELECTRICAL WORK
**************************************************************************
NOTE: Show the electrical characteristics, motor
starter type(s), enclosure type, and maximum rpm on
the drawings in the equipment schedules.
Where reduced-voltage motor starters are recommended
by the manufacturer or required otherwise, specify
and coordinate the type(s) required in Section 16402
INTERIOR DISTRIBUTION SYSTEM. Reduced-voltage
starting is required when full voltage starting will
interfere with other electrical equipment and
circuits and when recommended by the manufacturer.
Where adjustable speed drives (SD) are specified,
reference Section 16261 VARIABLE FREQUENCY DRIVE
SYSTEMS UNDER 600 VOLTS. The methods for
calculating the economy of using an adjustable speed
drive is described in UFC 3-520-01 INTERIOR
ELECTRICAL SYSTEMS.
**************************************************************************
a. Provide motors, controllers, integral disconnects, contactors, and
controls with their respective pieces of equipment, except controllers
indicated as part of motor control centers. Provide electrical
equipment, including motors and wiring, as specified in Section 16402
INTERIOR DISTRIBUTION SYSTEM. Manual or automatic control and
protective or signal devices required for the operation specified and
control wiring required for controls and devices specified, but not
SECTION 15895