CLASSIFICATION
Noncom-
bustible
Solids
Moisture
(Max.
Content
Value
Percent
(Max.
(Btu per
Type Description
Principle Components
by Weight
Percent)
Pound)
3
Garbage
Animal and vegetable
5
70
2,500
waste, restaurants,
hotels, markets;
institutional,
commercial, and
industrial sources
4
Animal
Carcasses, organs,
5
85
1,000
solids and
solid organic wastes;
organic
hospital, laboratory,
wastes
abattoirs, animal
pounds, and similar
sources
Loose
-
-
10,000
Paper
Loose
Wood
-
-
10,000
Classified
Highly-combustible
Material
waste, paper,
cardboard cartons
including up to 10%
plastics and treated
paper
-
-
7,000 to
10,000
2. Include ash analysis if available. Classified
material contents description may change as plastic
use increases. Check Incinerator Institute of
America for latest information.
**************************************************************************
**************************************************************************
NOTE: Insert appropriate Section number and title
in the blanks below using format per UFC 1-300-02.
**************************************************************************
Design mechanical cyclone-type dust collector(s) for operation with [the
incinerator(s) specified in [_____]] [incinerator(s) manufactured by
[_____], Type [_____], Model No. [_____]]. The incinerator is a [new]
[existing] installation capable of burning [_____] [kilogrampounds] per
hour [Mgtons per day] of type [0], [1], [2], [3], [4], [loose paper] [loose
operation will be between [_____] and [_____] [kilogrampounds] per hour [Mg
tons per day] of wastes. Incinerator combustion is controlled [manually]
[automatically]. Auxiliary fuel is [______]. Proposed or other existing
SECTION 15861N
Page 15