g.
Minimum hopper side slope angle degrees from horizontal, [60]
[_____].
h.
Minimum casing design pressure at [260 degrees C] [500 degrees F]
[_____], Pa inches water gage [+3735+15] [_____].
i.
Minimum casing design vacuum at [21 degrees C] [70 degrees C]
[_____], Pa inches water gage [-6225-25] [_____].
j.
Minimum casing design temperature, degrees C F [_____].
PART 2
PRODUCTS
2.1
MATERIALS
**************************************************************************
NOTE: Select the applicable paragraph(s) from the
following:
**************************************************************************
**************************************************************************
NOTE: Use these paragraphs for multitube collectors
150 mm 6 inch diameter collecting tubes may cause a
plugging problem. Designer must investigate flue
gas particulate size, distribution and tendency of
particulates to adhere to each other for the
specific project before selecting diameter of
collector tubes.
**************************************************************************
Multitube collector parts exposed to flue gas shall have a multilayer
internal lining having physical characteristics suitable for the service
and able to withstand abrasive and chemical action of flue gas and fly ash.
Insulating properties of lining shall be such that metal skin temperature
shall not exceed 343 degrees C 650 degrees F. All parts subject to
replacement. Materials used shall conform to the following requirements:
**************************************************************************
NOTE: Use ASTM A 242/A 242M steel when material is
subjected to continuous temperatures of 204 degrees C
400 degrees F or higher.
**************************************************************************
a.
Exterior shell: [ASTM A 242/A 242M Type 1] [or] [ASTM A 36/A 36M]
6 mm 1/4 inch minimum thickness.
b.
Hoppers:
[ASTM A 240/A 240M] 6 mm 1/4 inch minimum thickness.
**************************************************************************
NOTE: Use ASTM A 242/A 242M steel when material is
subjected to continuous temperatures of 204 degrees C
400 degrees F or higher.
**************************************************************************
c.
Collecting and outlet tube sheets:
[ASTM A 242/A 242M Type 1]
[or] [ASTM A 36/A 36M].
d.
Outlet tube:
[ASTM A 139 Steel] [or] [ASTM A 667/A 667M
SECTION 15861N
Page 19