outline or significant interface dimensions, certified list of
materials, adsorbent type and its certified test reports, welder
qualifications, certified test reports for all performance
requirements specified, certification of compliance with specified
SD-10 Operation and Maintenance Data
Filtration Unit Manuals[; G][; G, [_____]]
Operating and Maintenance Instructions[; G][; G, [_____]]
[Six] [_____] manuals listing step-by-step procedures required
for system startup, operation, shutdown, and routine maintenance,
at least 2 weeks prior to field training. The manuals shall
include the manufacturer's name, model number, parts list, list of
parts and tools that should be kept in stock by the owner for
routine maintenance including the name of a local supplier,
troubleshooting guide, and recommended service organization
(including address and telephone number) for each item of
equipment. Each service organization submitted shall be capable
of providing [4][_____] -hour on-site response to a service call
on an emergency basis.
1.5
SYSTEM DESCRIPTION
The CBR Air Filtration System shall include ASTM A 240/A 240M Type 304
stainless steel bag-in/bag-out housing, isolation dampers located where
indicated, roughing filter, pre-filter, , HEPA filters, carbon adsorbers,
[post-filter], in-place test sections, and a [blow-through] [draw-through]
fan unit mounted on a structural steel equipment skid as indicated. The
filtration system shall be provided with filtration element removal trays,
removable access doors, [filtration element banding kits,] pressure ports,
other appurtenances required for the specified operation. The filtration
system shall have physical dimensions suitable to fit the space allotted.
Sections of the filtration system shall be joined together in series to
make a system that meets the required capacity. The filtration system
shall be mechanically tested for leaks while in the factory. The
filtration system shall be suitable for continuous operation with an air
stream temperature of up to 57.2 degrees C 135 degrees F and suitable for
applicable requirements of ASME AG 1, ASME N509, ASME N-510-1, and UL 586.
Systems located in temperature controlled areas that filter conditioned air
or low temperature ambient air shall be [externally or internally insulated
as indicated] [of double walled construction with thermal insulation in the
interstitial space].
1.6
NAMEPLATES
Equipment shall have a nameplate that identifies the manufacturer's name,
address, type or style, model or serial number, and catalog number. Each
filtration element access door shall have a metal nameplate of the same
material as the filter housing, fastened to the exterior which states the
critical replacement components and part numbers for the equipment
contained inside. The nameplate shall include filtration element model
number, filtration element efficiency, and size. Each filtration element
housing shall be provided with an external metal pocket, for holding the
the housing. If housing is exposed to the weather, metal pocket shall be
SECTION 15860A
Page 8