UL listed; wattage, voltage, phase, and number of steps as indicated.
Provide control-circuit terminals and single source of power supply. Heater
5 Kw and larger shall be three-phase, with load balanced on each of the
three phases. Limit leaving air temperature below 60 degrees C at 15.5
degrees C 140 degrees F at 60 degrees F entering air.
2.1.4.1
Casing
Minimum [21] [_____] gage steel.
2.1.4.2
Heating Element
Nickel-chromium heating wire element, free from expansion noise and 60 Hz
hum. Embed element in magnesium-oxide insulating refractory. Seal element
in high-mass steel or corrosion-resisting metallic sheath with fins.
Enclose element ends in terminal box. Space fins at maximum six fins per
inch. Limit fin surface temperature 288 degrees C 550 degrees Fat any
point during normal operation.
2.1.4.3
Controls
Include limit controls for thermal overheat protection of heaters. For
remote thermostatic operation, provide contactor rated for 100,000 duty
control circuit for each heater.] Provide room thermostat for pilot duty.
2.1.4.4
Wiring
Completely factory-prewired to terminal strips, ready to receive branch
circuit and control connections for 60 degrees C 140 degrees F[copper] [or]
[aluminum] wiring.
[2.1.4.5
Accessories
**************************************************************************
NOTE: These accessories are not integral components
of electric unit heater. Delete this paragraph if
not required.
**************************************************************************
Provide fan switching devices to independently operate fan motor for summer
ventilation and winter heat recovery.
]2.2
**************************************************************************
NOTE: Check if Section 15768, "Electric Space
Heating Equipment," covers electric unit heater.
Recommend to cover unit heaters exclusively in this
section. Avoid redundant statement.
**************************************************************************
[Reflector-beam spread] [and] operating conditions as indicated. Provide
pre-wired control boxes, thermostats, and reflector [and duct] hangers.
2.2.1
Sheet Metal
[a.
Aluminum-Clad Steel:
ASTM A 463/A 463M, nominal thickness of
SECTION 15760N
Page 9