2.3.9
Ventilation Damper Assembly
**************************************************************************
NOTE: Delete requirement for ventilation damper
when outside air is supplied to the space by a
central system.
**************************************************************************
Operated by automatic actuator. Dampers shall close on unit shutdown or
loss of power and shall open on heating or cooling start-up.
2.3.10
Removable without use of tools, and shall filter both recirculated and
ventilating air.
2.3.11
Controls
Provide controls including, an adjustable thermostat, and switches, to
regulate room air temperature through control of refrigerant compressors or
heating elements. Controls shall at least have positions for off, high or
low fan speed for [heating] [and] [cooling], and fan only operation.
[Provide remote mounted night set-back thermostat.]
2.4
HEAT PUMPS, AIR TO AIR
**************************************************************************
NOTE: Equipment having a higher efficiency than
required by ASHRAE 90.1 or FS A-A-50502 shall be
specified if shown to be life-cycle cost effective.
**************************************************************************
**************************************************************************
NOTE: Refer to Military Handbook 1190, "Facility
Planning and Design Guide," for restrictions on heat
pump usage. Select the appropriate Type and Class
from the latest edition of FS A-A-50502.
**************************************************************************
FS A-A-50502, except as modified in this article; Type [_____], Class
[_____]. List units with capacities smaller than 39,555 watt 135,000 Btu/hr
in the [ARI DCUP]; in lieu of listing in the ARI Directory, a letter of
certification from ARI that the units have been certified and will be
listed in the next Directory will be acceptable. Provide factory assembled
units complete with accessories, wiring, piping, and controls. Provide
units with [outlet grilles.] [supplemental electric heaters.]
[humidifiers.] [air filters as specified in the paragraph entitled
"Filters."]
2.4.1
Energy Performance
In accordance with FS A-A-50502.
2.4.2
Air Coils
**************************************************************************
NOTE: Research project location conditions to
determine the environmental effects on finned tube
SECTION 15730N
Page 15