f.
Quantity of water feed to boiler.
g.
Boiler make, type, serial number, design pressure, and rated
capacity.
h.
Fuel burner make, model, and rated capacity; ammeter and voltmeter
readings for burner motor.
i.
[Circulating] [Condensate] [Vacuum] pump make, model, and rated
capacity, and ammeter and voltmeter readings for pump motor during
operation.
j.
Flue-gas temperature at boiler outlet.
k.
l.
Grade or type and calorific value of fuel.
m.
Draft at boiler flue-gas exit.
n.
Draft or pressure in furnace.
o.
Quantity of water circulated.
p.
Quantity of fuel consumed.
q.
Stack emission pollutants concentration.
otherwise directed. The Contractor shall furnish all instruments,
equipment, and personnel required for the tests and balancing. Fuels,
water, and electricity shall be obtained as specified in the SPECIAL
CONTRACT REQUIREMENTS. The Contractor shall provide a minimum of [_____] L
gallons of grade No. [_____] fuel oil. Operating tests shall demonstrate
that fuel burners and combustion and safety controls meet the requirements
of [ASME CSD-1] [ANSI Z21.13] [NFPA 85]
3.8.1
Water Treatment Testing
The boiler water shall be analyzed [prior to the acceptance of the
facility] [a minimum of once a month for a period of 1 year] by the water
treatment company. The analysis shall include the following information
recorded in accordance with ASTM D 596.
Date of Sample
[_____]
Temperature
[_____]
degrees C degrees F
Silica (SiO2)
[_____]
ppm (mg/1)
Insoluble
[_____]
ppm (mg/1)
Iron and Aluminum Oxides
[_____]
ppm (mg/1)
Calcium (Ca)
[_____]
ppm (mg/1)
Magnesium (Mg)
[_____]
ppm (mg/1)
Sodium and Potassium (Na and K)
[_____]
ppm (mg/1)
Carbonate (HCO3)
[_____]
ppm (mg/1)
Sulfate (SO4)
[_____]
ppm (mg/1)
Chloride (C1)
[_____]
ppm (mg/1)
Nitrate (NO3)
[_____]
ppm (mg/1)
Turbidity
[_____]
unit
pH
[_____]
Residual Chlorine
[_____]
ppm (mg/1)
SECTION 15569A
Page 75