b.
Air Operated Regulating Valves: Provide air operated control
valves for both the condensate and makeup water lines. Valves
shall have Class 125 or Class 150 rating with iron or semi-steel
bodies and 316 stainless steel internals. Provide condensate
valve which fails open on loss of air and makeup water valve with
an air lock mounted on valve diaphragm to hold valve in last
position on loss of air. Design valves for the following
conditions:
Condensate
Makeup Water
Valve size
[_____] mm
[_____] mm
Capacity
[_____] L/s
[_____] L/s
Maximum pressure drop
at above capacity
[_____] kPa (gage) [_____] kPa (gage)
Available pressure
[_____] kPa (gage) [_____] kPa (gage)
Minimum Cv at 100
percent open
[_____]
[_____]
Condensate
Makeup Water
Valve size
[_____] inch
[_____] inch
Capacity
[_____] gpm
[_____] gpm
Maximum pressure drop
at above capacity
[_____] psig
[_____] psig
Available pressure
[_____] psig
[_____] psig
Minimum Cv at 100
percent open
[_____]
[_____]
2.14.2.9
Low Pressure Steam Control
Provide an automatic control system to control steam to the deaerating
heater. Maintain steam pressure in the heater by modulating a pressure
reducing valve in the steam supply line. Control shall be local and remote
from the control panel.
a.
Controller: Adjustable proportional band, 0 to 103 kPa (gage) 15
psig brass bellows for input signal, and 20 to 103 kPa (gage) 3 to
15 psig output air pressure range, pilot controller complete with
control valve yoke.
b.
Pressure Reducing Station Control Valve: Provide a [_____] mm inch
air operated pressure reducing valve with proper internals to
pass a flow of [_____] kg per second pounds per hour of steam.
Steam at the valve inlet shall be [_____] kPa (gage) psig
saturated, and outlet shall be controlled at [_____] kPa (gage)
psig. Minimum steam flow shall be approximately [_____] kg per
second pounds per hour. Minimum valve Cv shall be [_____] at 100
percent open. Valve shall be Class 250 or Class 300 flanged, iron
SECTION 15501N