2.5.1.3
Electric Ignition System
**************************************************************************
NOTE: Natural gas pilot ignition system may be
considered only when natural gas is available at the
site.
**************************************************************************
**************************************************************************
NOTE: Choose this subparagraph or the subparagraph
below, entitled "Natural Gas Pilot Ignition System."
**************************************************************************
Burner shall be equipped with an electric ignition system. System shall be
either high energy ignition or glow rod type. Gas ignition system is not
acceptable. High energy ignition system shall use stored energy to develop
2000 Vdc pulses. Glow rod system shall use a low voltage, carbon rod
electrode which develops a tip temperature of 1427 degrees C 2600 degrees F.
Provide ignition system complete.
2.5.1.4
Natural Gas Pilot Ignition System
**************************************************************************
NOTE: Natural gas pilot ignition system may be
considered only when natural gas is available at the
site.
**************************************************************************
**************************************************************************
NOTE: Choose this subparagraph or the subparagraph
above, entitled "Electric Ignition System."
**************************************************************************
Provide a complete interrupted type natural gas-fired, spark ignited pilot
system for the burner assembly. Combustion air supply shall be from the
during startup periods. Lighter shall be arranged for easy removal and
servicing while boiler is in operation. Furnish ignitor complete with
spark rod and power pack. Power pack shall operate on 120 volt, 60 cycle,
single phase power. Provide gas piping, to one point of supply, including
gages, flame safety systems, interlocks and accessories to comply with
Industrial Risk Insurers' (I.R.I.) (formerly F.I.A.) requirements and
applicable codes and regulations.
2.5.1.5
Windbox
Construct of carbon steel plate not less than 10 gage thickness with 6 mm
1/4 inch thick front plate. Design windbox to provide even and uniform air
entrance into the burner register and seal weld to the boiler front wall.
Provide windbox with support legs.
2.5.1.6
Purge Connection
Provide [steam] [air] purge connection, properly valved, for purging oil
from gun prior to removal from burner.