(4) Conditioner side - coolant entering temperature.
(5) Regenerator side - entering air conditions (Db, Gr./LB).
(6) Regenerator side - discharge air conditions (Db, Gr./LB).
(7) Regenerator side - heat source temperature (Btu/hr).
(8) Running current, voltage and proper phase sequence for each
phase of all motors.
(9) The actual on-site setting of all operating and safety
controls.
3.3.2
Solid (Wheel) Desiccant System:
a.
Date and outside weather conditions (at least two parameters to
define the state of the outside air: DB, Gr./LB, Wb, relative
humidity).
b.
The load on the system based on the following:
(1) CFM entering the system (Process and Regeneration).
(2) Process side - entering air conditions (Db, Gr./LB).
(3) Process side - discharge air conditions (Db, Gr./LB).
(4) Process side - post coolant capacity (tons).
(5) Regenerator side - entering air conditions (Db, Gr./LB).
(6) Regenerator side - discharge air conditions (Db, Gr./LB).
(7) Regenerator side - heat source capacity (Btu/hr).
(8) Running current, voltage and proper phase sequence for each
phase of all motors.
(9) The actual on-site setting of all operating and safety
controls.
3.4
PIPE COLOR CODE MARKING
**************************************************************************
NOTE: Designer will coordinate color code marking
with Section 09900. Color code marking for piping
not listed in Table I of Section 09900, will be
added to the table.
**************************************************************************
Color code marking of piping shall be as specifried in Section09900 PAINTS
AND COATINGS.
3.5
INSPECTIONS
**************************************************************************
NOTE: It is strongly suggested that the customer
obtain a service contract on these units (solid and
liquid) to insure proper operation of the desiccant.
**************************************************************************
The manufacturer of the liquid desiccant system shall supply, free of
charge, testing of solution samples sent to them by the customer every two
months for the life of the equipment. The manufacturer of each type system
shall inspect the systems after one year of operation to insure the systems
are operating properly.
3.6
MANUFACTURER'S FIELD SERVICE
The services of a factory-trained representative shall be provided for
[_____] days. The representative shall advise on the proper operation and
SECTION 15500A