Fuel sample connectors
Venturi
Protective coatings
Fittings
Submit manufacturer's data including specifications and
performance test data. For fuel pumps, include actual diameter of
impeller being furnished and manufacturer's certified pump test
curves showing the characteristics over the entire operating range.
SD-08 Manufacturer's Instructions
Expansion joints
Filter separator units
Fuel quality monitors
Fuel meters
Flow controller
Fuel pumps
Relaxation tanks
Pantograph fueling stations
Venturi
Protective coatings
SD-10 Operation and Maintenance Data
Filter separator units, Data Package 2
Submit in accordance with Section 01781 OPERATION AND
MAINTENANCE DATA.
1.4
QUALIFICATIONS OF WELDERS
Each welder shall be qualified by test using equipment, procedures and a
base metal and electrode or filler wire from the same compatible group
number that will be encountered in field welding. Procedures and welders
shall be qualified in accordance with Section IX, ASME Boiler and Pressure
Vessel Code. Welders qualified by another employer may be accepted as
permitted by ASME B31.1. The Contracting Officer shall be notified 24
hours in advance of tests and the test shall be performed at the work site
if practicable. The Contracting Officer shall be furnished a copy of
qualified welders. The welder shall apply his assigned symbol near each
weld he makes as a permanent record.
SECTION 15194N
Page 12