SD-11 Closeout Submittals
Daily reports
1.3
QUALITY ASSURANCE
1.3.1
List of Qualified Installers
**************************************************************************
NOTE: Contractor's responsibility for
qualification, has been approved by NAVFAC HQ 021 in
accordance with the requirements of NAVFAC P-68. The
paragraph in the guide specification may be used
without any other NAVFAC approval or request for
waiver.
**************************************************************************
Submit [to the Contracting Officer] a manufacturer's certified list of
contractor personnel qualified to install and join the FRP piping.
Personnel not on the list will not be permitted to install and join FRP
piping.
1.3.2
Final Certification of FRP Pipe System
Upon completion of the project and before final acceptance, deliver [to the
Contracting Officer] a statement signed by the principal officer of the
contracting firm stating that the installation is satisfactory and in
complete accordance with the contract plans and specifications and the FRP
pipe manufacturer's prescribed procedures and techniques.
1.3.3
Glass Fiber Reinforced Plastic Fuel Systems
Certify the systems and products required to conform to the testing
requirements of MIL-P-29206 do and that all the products provided meet the
specified requirements and were manufactured with the same materials and
procedures as those tested.
1.3.4
Daily Reports
Submit a daily written report at the construction site. The report shall
note which employees were making FRP pipe joints. The original report
shall be signed by the Contractor and presented [to the Contracting
Officer] on the same day it is prepared. The report shall state whether or
not the condition and quality of the materials used and the installation of
the system is satisfactory in all respects. If the installation is
unsatisfactory, the reports shall state what corrective action has been
taken, or shall contain the recommendations for corrective action.
PART 2
PRODUCTS
2.1
MATERIALS
FRP piping system shall conform to the respective specifications and
standards and to the requirements specified herein. Pipe, fittings, and
joint adhesives shall be supplied by the same manufacturer. Threaded
fittings or mechanical couplings will not be permitted.
SECTION 15191N
Page 6