equal-percentage type valve to function properly.
**************************************************************************
**************************************************************************
Note: Control valve delta P @ design load (valve
full open) shall not be less than 34 kPa 5 psi. If
the control valve available differential pressure
drop with valve full open is less than 34 kPa 5 psi,
it is necessary to provide a pump sized for the
specific branch (loop) only, which does not affect
other system branches, to boost the available
pressure.
**************************************************************************
Two-way, single seated, equal percentage-flow type, industrial quality flow
regulating (control) valve conforming to the materials specified herein,
and size selected by the valve manufacturer for the following conditions:
a.
Maximum flow rate: [_____] L/s Gpm
b.
Minimum flow rate: [_____] L/s Gpm
c.
Internal pressure: [_____](maximum operating) kPa Psi
d.
Pressure differential @ design load:
[_____](open) delta p, kPa
Psi
e.
Pressure Differential @ minimum load: [_____] (closed) delta p,
kPa Psi (Equal to pump head or controlled differential pressure in
variable volume flow system)
Provide automatic operator with manual override (handwheel) and position
indicator.
2.1.7.4
Emergency Shutoff Valve
[HTW] [MTW] automatic, quick closing, ball valve located between the manual
[HTW] [MTW] supply shutoff valve and the system terminal unit inlet, with
pressure/temperature sensor located on the shell side. Emergency valve
shall automatically close when the pressure/temperature setting of the
shell side safety relief valve is reached. Emergency Valve shall be
normally open.
2.1.8
Strainers
Body materials shall conform to ASME B16.34, Fine Mesh type strainer and
trim shall be Type 304 or 316 stainless steel, selected for the service
specified herein.
2.1.9
Joints
2.1.9.1
Welded Joints
Joints between sections of pipe and between pipe and fittings shall be
welded. Joints between pipe and valves shall be welded or flanged. The
welding shall conform to requirements of paragraph entitled "Responsibility
of Contractor for Fusion Welding." Branch connections may be made with
either welding tees or forged branch outlet fittings, either being
acceptable without size limitations. Branch outlet fittings where used
SECTION 15184N
Page 12