Pipe fittings
[
[
Steam producer]
[
Expansion joints]
Information shall show details, dimensions, capacities, and
ratings.
SD-07 Certificates
Welding procedure specifications
Performance qualification record
Previous qualifications
Valves
Gaskets
PART 2
PRODUCTS
2.1
PIPE AND PIPE SYSTEM
**************************************************************************
NOTE: When individual branch loops require
circulating pumps due to constant volume plant
system design or insufficient available differential
pressure for terminal unit control valve in a
variable volume plant system design, designer must
provide appropriate pump specifications herein.
Pumps shall be carefully sized for the specific loop
only such that operation of the main plant system
and other branch loops is not affected.
**************************************************************************
**************************************************************************
NOTE: If it is necessary to provide for additional
thermal expansion of piping, designer may provide
design and specification for either expansion
loop(s) or mechanical expansion joints for the
particular service, however, expansion loop(s) are
preferred.
**************************************************************************
2.1.1
**************************************************************************
NOTE: Specify the maximum pressure and temperature
leaving the central heating plant. Note that some
corresponding saturation pressures at the supply
temperature, depending upon the method of plant
compressed gas pressurization methods produce
SECTION 15184N
Page 9