1.4
QUALITY ASSURANCE
1.4.1
Drawings: Monorail
Submit drawings showing the general arrangement of the track beam system,
including curves and switches, clearances, principal dimensions, details of
structural connections, air system details, and all component details.
Manufacturer's catalog data will suffice for items of standard manufacturer.
1.4.2
Certificates: Load Chain
Submit certification of minimum wire rope breaking strength for each hoist.
Where applicable, submit factory certification of the load chain rated
capacity.
1.4.3
Design Data: Design Calculations
Submit design calculations verifying the size of structural members,
structural supports (fittings, rods, brackets, and components), and lifting
beams for the track beam system. The calculations shall include stress and
1.5
MAINTENANCE
1.5.1
Monorail System
Submit data package for the entire monorail system in accordance with
Section 01781 OPERATION AND MAINTENANCE DATA.
PART 2
PRODUCTS
[2.1
FABRICATION AND CONSTRUCTION
**************************************************************************
NOTE: Select the applicable paragraph(s) from the
following:
**************************************************************************
The hoist and trolley shall conform to ASME HST-5 or ASME HST-6, [2] [3] [5]
metric ton ton, for [general service] [protected indoor] [all weather
outdoor (-18 to 38 degrees C0 degrees to 100 degrees F)] working
conditions. 2 metric ton ton design criteria shall apply to hoists of 2
metric ton ton, or less, rated lifting capacity. Hoists of 2, 3, or 5
metric ton ton rated capacity, shall be equipped with an automatic
mechanical load lowering brake.
2.1.1
Capacity
**************************************************************************
NOTE: When there is one hoist on one monorail
system, the monorail system capacity and the hoist
capacity will be comparable. When there is more
than one hoist on the monorail system, the capacity
of the monorail system should be comparable to the
total sum of the system hoists individual rated
capacity with the following exception:
1. There are positive monorail track beam stops to
restrict the approach of the hoists.
SECTION 14535N