this section. Select the first 13852 Section title
when using the basic NAVFAC guide specification
covering the subject work or select the second title
when using the EFD regional guide specification
covering the subject work.
**************************************************************************
Electrical work is specified in Section 16402 INTERIOR DISTRIBUTION SYSTEM
except for control [and fire alarm] wiring. [Fire alarm system is
specified in Section [13852N INTERIOR FIRE ALARM SYSTEM] ["Fire Alarm and
Fire Detecting Systems (Local)"]].
3.6.1
Wiring
Provide control wiring and connections, to fire alarm systems, under this
section in accordance with NFPA 70 and NFPA 72. Provide wiring in rigid
metal conduit or intermediate metal conduit, except electrical metallic
tubing may be used in dry locations not enclosed in concrete or where not
subject to mechanical damage. Do not run low voltage DC circuits in the
same conduit with AC circuits.
3.7
FLUSHING
Flush the piping system with potable water in accordance with NFPA 13.
Continue flushing operation until water is clear, but for not less than 10
minutes.
3.8
FIELD QUALITY CONTROL
compliance with drawings, specifications, and manufacturer's submittals.
Perform tests in the presence of the Contracting Officer to determine
conformance with the specified requirements.
3.8.1
Preliminary Tests
**************************************************************************
kPa or 345 kPa 200 psi or 50 psi above the maximum
working pressure when the maximum working pressure
is greater than 1034 kPa 150 psi.
**************************************************************************
Each piping system shall be hydrostatically tested at [1379 kPa (gage)]
[200 psig] [_____] in accordance with NFPA 11 and NFPA 13 and shall show no
leakage or reduction in gage pressure after 2 hours. The Contractor shall
conduct complete preliminary tests, which shall encompass all aspects of
system operation. Individually test all detectors, manual actuation
stations, alarms, control panels, and all other components and accessories
to demonstrate proper functioning. Test water flow alarms by flowing
water. When tests have been completed and all necessary corrections made,
submit to the Contracting Officer a signed and dated certificate, similar
to that specified in NFPA 13, attesting to the satisfactory completion of
all testing and stating that the system is in operating condition. Also
include a written request for a formal inspection and test.
3.8.2
Formal Inspection and Tests (Acceptance Tests)
The [_____] Division, Naval Facilities Engineering Command Fire Protection
SECTION 13957N
Page 39