surfaces as follows:
3.5.1
Foam Systems in Unfinished Areas
**************************************************************************
NOTE: For facilities located in a marine
environment specify SSPC SP 11 cleaning and specify
a second topcoat.
**************************************************************************
Unfinished areas are defined as locations exposed to weather, attic spaces,
spaces above suspended ceilings, crawl spaces, foam rooms, pump rooms, pipe
chases, and other spaces where ceilings are not painted or not constructed
of a prefinished material. Paint primed surfaces with [one] [two] coat[s]
of FS TT-E-489 red enamel applied to a minimum dry film thickness of 0.04 mm
1.5 mils. Paint surfaces exposed to weather with two coats of red enamel
as specified herein.
3.5.2
Foam Systems in All Other Areas
**************************************************************************
NOTE: For facilities located in a marine
environment specify SSPC SP 11 cleaning and specify
a second topcoat.
**************************************************************************
Paint primed surfaces with two coats of paint to match adjacent surfaces,
except paint valves and operating accessories with [one] [two] coat[s] of
FS TT-E-489 red enamel applied to a minimum dry film thickness of 0.04 mm
1.5 mils. Provide piping with 50 mm 2 inch wide red bands spaced at maximum
6 meters 20 foot intervals throughout the piping systems. Bands shall be
red enamel or self adhering red plastic tape.
3.5.3
Piping Labels
Provide permanent labels in foam rooms, spaced at 6 meters 20 foot maximum
intervals along pipe, indicating "WATER", "FOAM CONCENTRATE", and "FOAM
SOLUTION" on corresponding piping.
3.5.4
Field Touch-Up
Clean damaged areas of shop coated tanks in accordance with SSPC SP 11 and
coat cleaned areas with the same materials used for the shop applied
coating system.
3.6
ELECTRICAL WORK
**************************************************************************
NOTE: Edit Section 16402, "Interior Distribution
System" and include as part of the project
specification.
**************************************************************************
**************************************************************************
NOTE: When project includes requirement for a
building fire alarm system, include Section 13852 in
the project specification. When project requires
only tying into an existing building fire alarm
system, fire alarm wiring should be specified in
SECTION 13957N
Page 38