shall be incorporated into the design. Reference to "authority having
jurisdiction" shall be interpreted to mean the Contracting Officer.
1.12
SPARE PARTS
The Contractor shall submit spare parts data for each different item of
material and equipment specified.
The data shall include a complete list
of parts and supplies, with current unit prices and source of supply, and a
list of parts recommended by the manufacturer to be replaced after 1 year
and 3 years of service. A list of special tools and test equipment
required for maintenance and testing of the products supplied by the
Contractor shall be included.
PART 2
PRODUCTS
2.1
STANDARD PRODUCTS
Materials and equipment shall be standard products of a manufacturer
regularly engaged in the manufacture of such products and shall essentially
duplicate items that have been in satisfactory use for at least 2 years
prior to bid opening.
2.2
NAMEPLATES
All equipment shall have a nameplate that identifies the manufacturer's
name, address, type or style, model or serial number, and catalog number.
2.3
REQUIREMENTS FOR FIRE PROTECTION SERVICE
Materials and equipment shall have been tested by Underwriters
Laboratories, Inc. and listed in UL Fire Prot Dir or approved by Factory
Mutual and listed in FM P7825a and FM P7825b. Where the terms "listed" or
"approved" appear in this specification, such shall mean listed in UL Fire
Prot Dir or FM P7825a and FM P7825b.
2.4
**************************************************************************
NOTE: The drawings must show the service connection
details and the underground water mains for the
sprinkler system. The drawings must show details of
the water service point-of-entry into the building
and through the floor slab, and underground piping
restraints, including number and size of restraining
rods and thrust blocks.
**************************************************************************
2.4.1
Pipe
Piping from a point 150 mm 6 inches above the floor to [a point 1500 mm 5
feet outside the building wall] [the point of connection to the existing
water mains] shall be ductile iron with a rated working pressure of [1034]
[1207] [_____] kPa [150] [175] [_____] psi conforming to AWWA C151, with
cement mortar lining conforming to AWWA C104. Piping more than 1500 mm 5
feet outside the building walls shall comply with Section 02510A WATER
DISTRIBUTION SYSTEM.
SECTION 13945A
Page 18