FOUNDATION FOR CROSS-CONNECTION CONTROL AND HYDRAULIC RESEARCH
(FCCCHR)
FCCCHR List
(continuously updated) List of Approved
Backflow Prevention Assemblies
MANUFACTURERS STANDARDIZATION SOCIETY OF THE VALVE AND FITTINGS
INDUSTRY (MSS)
MSS SP-58
(2002) Pipe Hangers and Supports -
Materials, Design and Manufacture
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 13
(2002) Installation of Sprinkler Systems
NFPA 24
(2002) Installation of Private Fire
Service Mains and Their Appurtenances
NFPA 70
(2005) National Electrical Code
UNDERWRITERS LABORATORIES (UL)
UL 262
Service
UL 789
(2004) Indicator Posts for Fire-Protection
Service
UL Fire Prot Dir
(2004) Fire Protection Equipment Directory
1.2
DEFINITION
a.
Year 2000 compliant - means computer controlled facility
components that accurately process date and time data (including,
but not limited to, calculating, comparing, and sequencing) from,
into, and between the twentieth and twenty-first centuries, and
the years 1999 and 2000 and leap year calculations.
[1.3
SYSTEM DESCRIPTION
Design and provide [new and modify existing] automatic wet pipe fire
extinguishing sprinkler systems for complete fire protection coverage
throughout [_____].
]1.4
SPRINKLER SYSTEM DESIGN
**************************************************************************
NOTE: Areas smaller than 279 sq meters 3,000 sq ft,
use pipe schedules. Areas larger than 279 sq meters
3,000 sq ft, use pipe schedules or hydraulic
calculations. Open areas larger than 929 sq meters
10,000 sq ft, use hydraulic calculations. When
hydraulic calculations are not included, delete
paragraphs entitled "Water Distribution," "Density
of Application of Water," "Sprinkler Discharge
Area," "Outside Hose Allowances," "Friction Losses,"
and "Water Supply."
**************************************************************************
SECTION 13930N
Page 5