submittal is sufficiently important or complex in
context of the project.
For submittals requiring Government approval on Army
projects, a code of up to three characters within
the submittal tags may be used following the "G"
designation to indicate the approving authority.
Codes for Army projects using the Resident
Management System (RMS) are: "AE" for
Architect-Engineer; "DO" for District Office
(Engineering Division or other organization in the
District Office); "AO" for Area Office; "RO" for
Resident Office; and "PO" for Project Office. Codes
following the "G" typically are not used for Navy
projects.
Submittal items not designated with a "G" are
considered as being for information only for Army
projects and for Contractor Quality Control approval
for Navy projects.
**************************************************************************
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are [for Contractor Quality Control
approval.][for information only. When used, a designation following the
"G" designation identifies the office that will review the submittal for
the Government.] The following shall be submitted in accordance with
Section 01330 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Shop Drawings[; G][; G, [_____]]
[Three] [_____] copies of the Sprinkler System Shop Drawings, no
later than [21] [_____] days prior to the start of sprinkler
system installation.
As-Built Drawings
As-built shop drawings, at least [14] [_____] days after
completion of the Final Tests. The Sprinkler System Drawings
shall be updated to reflect as-built conditions after all related
work is completed and shall be on reproducible full-size mylar
film.
SD-03 Product Data
Fire Protection Related Submittals
A list of the Fire Protection Related Submittals, no later than
[7] [_____] days after the approval of the Fire Protection
Specialist.
Sway Bracing[; G][; G, [_____]]
For systems that are required to be protected against damage
from earthquakes, load calculations shall be provided for sizing
of sway bracing.
SECTION 13930A
Page 12