Manufactured Homes
NFPA 13R
(2002) Installation of Sprinkler Systems
in Residential Occupancies Up to and
Including Four Stories in Height
NFPA 1963
(2003) Fire Hose Connections
NFPA 24
(2002) Installation of Private Fire
Service Mains and Their Appurtenances
NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES
(NICET)
NICET 1014-7
(2003) Program Detail Manual for
Certification in the Field of Fire
Protection Engineering Technology (Field
Code 003) Subfield of Automatic Sprinkler
System Layout
UNDERWRITERS LABORATORIES (UL)
UL 668
(2004) Hose Valves for Fire Protection
Service
UL Bld Mat Dir
(2004) Building Materials Directory
UL Fire Prot Dir
(2004) Fire Protection Equipment Directory
1.2
GENERAL REQUIREMENTS
**************************************************************************
NOTE: Residential Occupancies: NFPA 13R is
applicable for residential occupancies up to and
including 4 stories in height. This standard should
be referenced and followed only for such
occupancies. NFPA 13R differs from NFPA 13 relative
to type of sprinkler, design criteria, sprinkler
coverage, etc. Care must be taken when using this
specification for residential occupancies to assure
that the final project specification clearly
**************************************************************************
Wet pipe sprinkler system shall be provided in [all areas of the building]
[areas indicated on the drawings] [_____]. The sprinkler system shall
provide fire sprinkler protection for the entire area. Except as modified
herein, the system shall be designed and installed in accordance with [NFPA
13] [NFPA 13R]. Rack sprinklers shall be in accordance with NFPA 13. Pipe
sizes which are not indicated on drawings shall be determined by hydraulic
calculation. The Contractor shall design any portions of the sprinkler
system that are not indicated on the drawings including locating
sprinklers, piping and equipment, and size piping and equipment when this
information is not indicated on the drawings or is not specified herein.
The design of the sprinkler system shall be based on hydraulic
calculations, and the other provisions specified herein.
SECTION 13930A
Page 9