[i.
Fire pump loss of power/phase reversal]
[j. [_____]]
]2.3
NAMEPLATES
Major components of equipment shall have the manufacturer's name, address,
type or style, model or serial number, catalog number, date of
installation, installing Contractor's name and address, and the contract
number provided on a new plate permanently affixed to the item or
equipment. Major components include, but are not limited to, the following:
a.
FACPs
b.
c.
Printer
Furnish to obtain approval by the Contracting Officer before installation.
Obtain approval by the Contracting Officer for installation locations.
Nameplates shall be etched metal or plastic, permanently attached by screws
to panels or adjacent walls.
2.4
WIRING
Provide wiring materials under this section as specified in Section 16402
INTERIOR DISTRIBUTION SYSTEM with the additions and modifications specified
herein.
PART 3
EXECUTION
3.1
INSTALLATION OF FIRE ALARM INITIATING AND INDICATING DEVICES
a.
FACP: Locate the FACP [where indicated on the drawings] [_____].
[Recess] [Semi-recess] [Surface mount] the enclosure with the top
of the cabinet 1830 mm 6 feet above the finished floor or center
the cabinet at [1525] [_____] mm [5] [_____] feet, whichever is
lower. Conductor terminations shall be labeled and a drawing
containing conductors, their labels, their circuits, and their
interconnection shall be permanently mounted in the FACP.
b.
Manual Stations: Locate manual stations [as required by NFPA 101
and NFPA 72] [where shown on the drawings] [_____]. Mount
stations so that their operating handles are 1220 mm 4 feet above
the finished floor. Mount stations so they are located no farther
than [1525] [_____] mm [5] [_____] feet from the exit door they
serve, measured horizontally.
c.
Notification Appliance Devices: Locate notification appliance
devices [as required by NFPA 72] [where shown on the drawings].
Mount assemblies on walls 2030 mm 80 inches above the finished
floor or 150 mm 6 inches below the ceiling whichever is lower.
[Ceiling mounted speakers shall conform to NFPA 72].
[d.
Smoke and Heat Sensors: Locate sensors [as required by NFPA 72
and their listings] [as shown on the drawings] on a 4 inch
mounting box. Sensors located on the ceiling shall be installed
not less than 100 mm 4 inches from a side wall to the near edge.
SECTION 13855N
Page 37