trouble condition shall be printed. The printout shall include
the type of signal, the circuit or device reporting, the date, and
the time of the occurrence. The printer shall differentiate alarm
signals from other printed indications. When the system is reset,
this condition shall also be printed including the same
information concerning device, location, date, and time. Provide
a means to automatically print a list of existing alarm,
supervisory, and trouble conditions in the system. If a printer
is off-line when an alarm is received, the system shall have a
buffer to retain the data and it shall be printed when the printer
is restored to service. The printer shall have an indicator to
alert the operator that the paper has run out.
][2.2.17
Firefighter Telephone Communication System
**************************************************************************
with remote telephone stations in each stair at each
floor landing, in each elevator lobby on each floor,
and in elevator cabs. In addition, provide them at
specific locations containing essential fire
protection equipment, such as the fire pump room and
**************************************************************************
a.
Provide a firefighter telephone system as follows:
(1) Provide a firefighter telephone communication system with
complete, common talk, closed circuits. The system shall include,
but not be limited to, a master control station mounted in the
fire alarm control panel, a power supply and standby battery
system, and remote telephone stations.
(2) Provide a master control station which shall provide power,
supervision, and control for wiring, components, and circuits.
The act of lifting any remote telephone hand set from its cradle
shall cause both a visual and audible signal to annunciate at the
master control station. Removing the hand set at the master
control station and depressing a button at the remote telephone
hand set shall cause the automatic silencing of the audible
signal. Communication between the master control station hand set
and any/or all remote hand sets shall require the depressing of a
push-to-talk switch located on any/all remote hand sets. During
the time that the master control hand set is removed from its
cradle it shall be possible to communicate between five remote
to monitor any conversation in progress and join the conversation
by pressing the push-to-talk button. It shall not be possible to
communicate between two or more remote hand sets with the master
control station hand set in its cradle. The master control
station hand set shall be red in color and equipped with a 5-foot
long strain-relieved coiled cord. Wiring connections shall be
made to terminal strips. The master control station shall monitor
wire and connections for any opens, shorts, or grounds which would
render the system inoperable or unintelligible. The master
control station shall be equipped with a silencing switch and
ring-back feature such that any audible trouble signal can be
silenced and shall be so indicated by the lighting of an amber
LED. Once any trouble condition has been corrected, the amber LED
SECTION 13855N
Page 32