the coded device and cause operation of the system trouble signal.]
[h.
HVAC shutdown bypass switch. Operation of the switch shall allow
HVAC system to operate with detectors in alarm and shall cause
operation of system trouble signals.]
2.2.1.1
Main Annunciator
Provide integral with the control panel. Provide separate alarm and
trouble lamps for each zone (initiating circuit) as indicated below and
[_____] spares, located on the exterior of the cabinet door or visible
through the cabinet door. Lamps shall be Light Emitting Diode (LED) type.
Zone modules for spare zones shall be provided in the control panel.
Supervision will not be required provided a fault in the annunciator
circuits results only in loss of annunciation and will not affect the
shall provide specific identification of the [zone] [area] [device] by
means of a permanent label. Provide engraved, silk screened, or
machine-made labels. Handwritten labels are prohibited. In no case shall
zone identification consist of the words "Zone 1," "Zone 2," etc., but
shall consist of the description of the [zone] [area] [device].
2.2.1.2
Initiating Zones
**************************************************************************
NOTE: List zones with a brief description of each
zone; e.g. "Zone 1: First Floor, West Wing," etc.
Expand this list as necessary to identify all the
zones required for the building. Provide separate
zones for smoke detectors. Always specify separate
zones for duct detectors, extinguishing systems, and
sprinkler or fire pump supervision (if provided).
Do not put devices on different floors on the same
zone. When choosing second option, place the
following chart on the fire alarm contract drawing.
**************************************************************************
[Arrange as follows:
Zone No.
Description
[_____]
[_____]
[_____]
[_____]
[_____]
[_____]
[_____]
[_____]
[_____]
[_____]
[_____]
[_____]]
[Arrange as shown.]
2.2.1.3
Remote Annunciator Panel
**************************************************************************
NOTE: Locate panel at or near the building entrance
SECTION 13852N
Page 20