submittal is sufficiently important or complex in
context of the project.
For submittals requiring Government approval on Army
projects, a code of up to three characters within
the submittal tags may be used following the "G"
designation to indicate the approving authority.
Codes for Army projects using the Resident
Management System (RMS) are: "AE" for
Architect-Engineer; "DO" for District Office
(Engineering Division or other organization in the
District Office); "AO" for Area Office; "RO" for
Resident Office; and "PO" for Project Office. Codes
following the "G" typically are not used for Navy
projects.
Submittal items not designated with a "G" are
considered as being for information only for Army
projects and for Contractor Quality Control approval
for Navy projects.
**************************************************************************
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for [Contractor Quality Control
approval.] [information only. When used, a designation following the "G"
designation identifies the office that will review the submittal for the
Government.] The following shall be submitted in accordance with Section
01330 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Fire Alarm Reporting System[; G][; G, [_____]]
consisting of a complete list of equipment and material, including
manufacturer's descriptive and technical literature, catalog cuts,
show layouts based on typical detectors. The contractor shall
check the layout based on the actual detectors to be installed and
for the equipment furnished, equipment layout, and any other
details required to demonstrate that the system has been
coordinated and will properly function as a unit.
Wiring for Systems[; G][; G, [_____]]
Professional Engineer, showing all points of connection. Diagram
shall include connections between system devices, appliances,
control panels, supervised devices, an all equipment that is
activated or controlled by the panel.
SD-03 Product Data
Battery
Substantiating battery calculations for supervisory and alarm
SECTION 13852A
Page 5