information pamphlet (EPA 747-K-99-001 "Protect Your Family From Lead in
Your Home") prior to commencing the renovation work for each affected unit
per 40 CFR 745 Subpart E.]
[
c. Notification of the Commencement of [LBP] Hazard Abatement
**************************************************************************
NOTE: In some states, notification of lead-based
paint hazard abatement work by the contractor must
be made prior to work. Research if prior
notification is required for the locality where work
is conducted.
**************************************************************************
[Submit a copy of the notification of the commencement of [LBP] hazard
abatement to [______] according to the procedures established by [______].]]
3.1.1.2
Boundary Requirements
a. Provide physical boundaries around the lead control area by roping
off the area designated in the work plan or providing curtains,
portable partitions or other enclosures to ensure that lead will not
escape outside the lead control area.
b. Warning Signs - Provide warning signs at approaches to lead control
areas. Locate signs at such a distance that personnel may read the sign
and take the necessary precautions before entering the area. Signs
shall comply with the requirements of 29 CFR 1926.62.
3.1.1.3
Furnishings
**************************************************************************
NOTE: Verify with the activity furniture/equipment
requirements.
**************************************************************************
[ The Government will remove furniture and equipment from the building before
lead-based paint removal work begins.]
[ Existing [furniture] [and] [equipment] is lead contaminated,
[decontaminate] [dispose of as lead contaminated waste].]
3.1.1.4
Shut down, lock out, and isolate HVAC systems that supply, exhaust, or pass
through the lead control areas. Seal intake and exhaust vents in the lead
control area with 0.15 mm 6 mil plastic sheet and tape. Seal seams in HVAC
components that pass through the lead control area. [Provide temporary HVAC
system for areas in which HVAC has been shut down outside the lead control
area.]
3.1.1.5
Decontamination Shower Facility
Provide clean and contaminated change rooms and shower facilities in
accordance with this specification and 29 CFR 1926.62.
SECTION 13283N