PART 3
EXECUTION
3.1
ERECTION
Dissimilar materials which are not compatible when contacting each other
shall be insulated from each other by means of gaskets or insulating
compounds. Improper or mislocated drill holes in panels shall be plugged
with an oversize screw fastener and gasketed washer; however, panels with
an excess of such holes or with such holes in critical locations shall not
be used. Exposed surfaces shall be kept clean and free from sealant, metal
cuttings, excess material from thermal cutting, and other foreign
materials. Exposed surfaces which have been thermally cut shall be
finished smooth within a tolerance of 3 mm.1/8 inch. Stained, discolored
or damaged sheets shall be removed from the site. Welding of steel shall
conform to AWS D1.1/D1.1M; welding of aluminum shall conform to AA ADM1.
3.1.1
Framing Members and Anchor Bolts
Onsite flame cutting of framing members, with the exception of small access
holes in structural beam or column webs, will not be permitted. Concrete
work is specified in Section [03300A CAST-IN-PLACE STRUCTURAL CONCRETE][
03300N CAST-IN-PLACE CONCRETE]. Anchor bolts shall be accurately set by
template while the concrete is in a plastic state. Members shall be
accurately spaced to assure proper fitting of panels. As erection
progresses, the work shall be securely fastened to resist the dead load and
wind and erection stresses.
3.1.2
Roofing and Siding Installation
**************************************************************************
NOTE: When factory insulated panels are used, this
paragraph will be modified as necessary to cover
their installation.
**************************************************************************
Siding shall be applied with the longitudinal configurations in the
vertical position. Roofing shall be applied with the longitudinal
configurations in the direction of the roof slope. Accessories shall be
fastened into framing members, except as otherwise approved. Closure
strips shall be provided where necessary to provide weathertight
construction. Fastener and fastener spacing shall be in accordance with
manufacture design.
3.1.3
Installation of Gutters and Downspouts
Gutters and downspouts shall be rigidly attached to the building. Spacing
of cleats for gutters shall be 400 mm 16 inches maximum. Spacing of
brackets and spacers for gutters shall be 1 m 36 inches maximum. Supports
for downspouts shall be spaced according to manufacturer's recommendations.
3.1.4
Louvers and Ventilators
Louvers and ventilators shall be rigidly attached to the supporting
construction to assure a weather tight installation.
3.1.5
Doors and Windows
Doors and windows, including frames and hardware, shall be securely
anchored to the supporting construction, shall be installed plumb and true,
SECTION 13121
Page 18