2.6.1
Hinged Doors
Hinged doors and frames shall receive a galvanic coating and factory primer
and shall conform to [SDI A250.8, Type, Grade and size as indicated] [the
requirements of Section 08110 STEEL DOORS AND FRAMES]. Exterior doors
shall have top edges closed flush and sealed against water penetration.
Hardware shall be [as scheduled [herein] [on the drawings]] [as specified
in Section 08710 DOOR HARDWARE].
2.6.2
Sliding Doors
Sliding doors shall be of the metal framed or self-framing metal type.
Covering shall be of same material and finish as the siding, except that
heavier gauge material shall be used if required to provide rigidity. All
hardware necessary for the complete installation of the doors shall be
furnished. Accessories shall include galvanized steel track, brackets,
permanently lubricated dual wheel trolley hangers, operating handle, slide
bolt latch assembly permitting padlocking from either inside or outside of
building, and rubber or elastomeric weather stripping.
2.6.3
Overhead Rolling Doors
Overhead rolling doors shall conform to the requirements of Section 08330
OVERHEAD ROLLING DOORS. Hardware shall be [as scheduled [herein] [on the
drawings]] [as specified in Section 08710 DOOR HARDWARE].
2.6.4
Sectional Overhead Doors
Sectional overhead doors shall conform to the requirements of Section 08361
SECTIONAL OVERHEAD DOORS. Hardware shall be [as scheduled [herein] [on the
drawings]] [as specified in Section 08710 DOOR HARDWARE].
2.6.5
Vertical Lift Doors
Vertical lift doors shall conform to the requirements of Section 08370
VERTICAL LIFT DOORS. Hardware shall be [as scheduled [herein] [on the
drawings]] [as specified in Section 08710 DOOR HARDWARE].
2.7
INSULATION
**************************************************************************
NOTE: Flame spread and smoke development ratings of
insulation, to include facing, must comply with the
requirements of MIL HDBK 1008C. Exposed insulation
must be faced, mineral fiber type, only; cellular
plastic insulation will not be exposed.
If prefabricated insulated sandwich panels are used
for siding and roofing, delete this paragraph in its
entirety.
**************************************************************************
Thermal resistance of insulation shall be not less than the R-values shown
on the contract drawings. R-values shall be determined at a mean
temperature of 24 degrees C 75 degrees F in accordance with ASTM C 518.
[Roof] [Roof and wall] insulation shall be a standard product with the
insulation manufacturer, factory marked or identified with insulation
manufacturer's name or trademark and R-value. [Insulation] [Insulation
SECTION 13121
Page 15