odorless, free from mold, and not become a source of food and shelter for
insects. Panels shall be not less than 200 mm 8 inches wide and shall be
in one piece for unbroken wall heights.
2.2.6
Factory Color Finish
Wall and roof panels shall have a factory applied [polyvinylidene fluoride]
[_____] finish on the exposed side. The exterior finish shall consist of a
baked-on topcoat with an appropriate prime coat. Color shall match the
color indicated on the drawings. The exterior coating shall be a nominal
0.025 mm 1 mil thickness consisting of a topcoat of not less than 0.018 mm
0.7 mil dry film thickness and the paint manufacturer's recommended primer
of not less than 0.005 mm 0.2 mil thickness. The interior finish shall
consist of the manufacturer's recommended thickness primer coating.
2.2.7
Accessories
Flashing, trim, metal closure strips and curbs, fascia, caps, diverters,
and similar metal accessories shall be the manufacturer's standard
products. Exposed metal accessories shall be finished to match the
building finish. Molded closure strips shall be bituminous-saturated
fiber, closed-cell or solid-cell synthetic rubber or neoprene, or polyvinyl
chloride premolded to match configuration of the roofing or siding and
shall not absorb or retain water.
2.3
WALL LINERS
**************************************************************************
NOTE: Height of wall liners will be shown on
drawings.
**************************************************************************
Wall liners shall be 0.6 mm 0.024 inch thick minimum for aluminum or 0.45 mm
0.018 inch thick minimum for steel. Matching metal trim shall be provided
[at base of wall liner,] [at top of wall liner,] [around openings in walls]
[and over interior and exterior corners]. Wall liners shall have [the same
factory color finish as specified for the exterior face of the wall
panels.] [manufacturer's standard finishes.] Colors shall be [selected
from manufacturer's standard finishes] [as indicated].
2.4
FASTENERS
Fasteners shall be as recommended by the manufacturer to meet the design
strength requirements.
2.5
WINDOWS
Windows shall be as recommended by the manufacturer; windows shall be
indicated on the drawings.
2.6
DOORS
**************************************************************************
NOTE: Select door types for commercially framed
openings. Delete unused door types, and renumber
paragraphs as appropriate. Referenced door
specification sections will be made a part of the
**************************************************************************
SECTION 13121
Page 14